November 25, 2026 · Graham Wenz, Matt Kapelewski, Pallavi Sharma and Steven Bennett, Orbital Industries

AI racks due in 2027 are specified at around 600 kW, almost 2.5x higher than today's most powerful rack, NVIDIA's Vera Rubin NVL72. Almost all of that power leaves the rack as heat, and most of it has to be extracted straight off the chips.
Today that job usually falls to single-phase direct-to-chip cooling, which pumps water or a water-glycol mix through a cold plate on each chip. The coolant warms by a few degrees and returns to a coolant distribution unit (CDU), which passes the excess heat to the facility water loop.
Single-phase cooling is the industry's proven, cost-effective standard, and it handles current GPU packages comfortably up to 2,300 W. It has kept up by pushing more water through the same plates, but every increase in flow means more pumping power, larger manifolds, and higher pressure drop. The generation after is expected to draw 3,600 W and climbing, and with GPU makers now shipping a new GPU architecture every year, operators need an additional tier that can carry more heat without more flow. That makes two-phase the natural next step.
Two-phase direct-to-chip cooling replaces the water with a fluid, usually electrically insulating, that boils on the cold plate rather than just warming up. Boiling a kilogram of a typical low-pressure refrigerant at 25°C absorbs about 170 to 210 kJ, while warming a kilogram of water by 10°C only absorbs about 42 kJ. That means a two-phase loop can carry away the same heat with far less flow, at a nearly constant temperature across the plate.
Most of the fluids used for two-phase cooling today are PFAS (per- and polyfluoroalkyl substances). The carbon-fluorine bond that makes PFAS stable inside a cooling loop also makes them persist once they escape it, which is why they're called forever chemicals. 3M, a major supplier of those fluids, stopped making PFAS at the end of 2025. They have since agreed to pay up to $7.35bn to settle personal injury claims over PFAS groundwater contamination, on top of the $10.3bn they agreed in 2023 over contaminated US public drinking water systems. Regulation is tightening too. The EU is working toward a broad PFAS restriction that includes fluorinated refrigerants, and Minnesota and Maine plan to ban almost all products with intentionally added PFAS from 2032, though Maine gives refrigerants and cooling equipment until 2040.
That leaves the industry needing new, non-PFAS fluids, and designing one is challenging. It still has to meet the normal refrigerant requirements, including a low global warming potential (GWP), boil at the right temperature for the chip at a practical loop pressure, survive thousands of boiling cycles without breaking down, and remove heat fast enough for high-power GPUs. And in two-phase, a new fluid means new hardware. In single-phase cooling you can pick a coolant from a catalog and size the hardware around it. In two-phase, the fluid's properties reach into every component of the loop, so a choice made in one place shows up as a constraint somewhere else.
Orbital Industries decided to start from the fluid instead, building our two-phase direct-to-chip system around a non-PFAS fluid and designing that fluid, the cold plate, and the CDU as one problem.
We discovered a new non-PFAS fluid for two-phase cooling using CurieOS, the AI operating system we built for science and engineering. It's a molecule no one had identified before. CurieOS ran the screen against the requirements above while Orb, our AI model for accelerated simulation, modeled each candidate, so we could cover far more chemistry than lab work alone could test. Our chemists and engineers then validated the result.
Choosing the fluid first matters because, on the cold plate, the coolant boils at its saturation temperature, which stays roughly constant and is set by the loop pressure. Pick the fluid and you've picked the pressure. Set two commercial refrigerants to boil at 25°C, and one needs the loop held at 74 kPa, below atmospheric pressure, so any leak pulls air in. The other needs 194 kPa, so every fitting, seal, and connector has to hold positive pressure, even though both loops cool the same chip to the same temperature.
These properties trade against each other. A fluid with a high saturation temperature can still be the wrong choice if it forces the loop below atmospheric pressure, like the 74 kPa case above, or needs wider return lines because of its low vapor density.
3D model of a prototype cold plate assembly for 2-phase D2C cooling with liquid supply, vapor collection and enhanced surfaces for boiling.
Boiling heat transfer depends on the fluid and the surface as a pair. Surface tension and contact angle control how bubbles form and leave the surface. If vapor can't clear fast enough, or the liquid can't be replenished quickly enough, an insulating layer can form near the surface and the local temperature climbs, leading to local dry-out. Bubble departure diameters can differ by an order of magnitude between fluid-surface pairings, so fin pitch, pin height, channel width, and liquid supply geometry that work for one fluid can underperform with another.
We learned how large that effect is by testing our boiling simulation against hundreds of runs on our own rigs, calibrating our models at atmospheric pressure, spanning 150 to 2,000 W of heat input and flow rates from 0.1 to 1.5 L/min. Graham Wenz and Rick Rothbart described that pipeline in July, along with the jet impingement lid we took from V1 to V3.
Liquid supply lid and cold plate assembly, machined and assembled in-house
So we evaluate every cold plate geometry with a specific fluid. Change the fluid and its liquid and vapor properties change, and so does loop pressure, so the ranking of designs can change with it. Simulation narrows the field, and the test rig still makes the final call, since interface resistance, manufacturing tolerances, and boiling instabilities are hard to capture in any model.
CurieOS ties that loop together: we design each cold plate in it, machine the plate in house, and test it on our rig, and CurieOS checks every result against the simulation. It has logged more than 2,000 rig runs automatically, so each test feeds straight into the next round of designs and we get through more iterations in the same window.
Our Director of Engineering Graham Wenz at our test rig
That loop has now produced a result at the power density the next generation of chips demands. Our latest cold plate assembly, based on a micro-structured evaporator with an optimized inlet/outlet manifold lid design, removed 76 W/cm² while holding the chip/case temperature below 70°C, matching the average heat flux of a Rubin GPU at its 2,300 W maximum load. It did that with a flow rate per kilowatt roughly 40% below the OCP recommendation for single-phase direct-to-chip cooling, which is the flow reduction two-phase promises, measured on our own hardware.
The way the fluid boils sets the cold plate's internal geometry, the size of the condenser that turns vapor back to liquid in the CDU, and the pressure the whole loop runs at. We design all three together in CurieOS. Its context graph links the fluid, cold plate, and CDU work and updates as new information arrives, so a change in one domain shows up in the other two.
Each new thermal design power target moves the operating point again. A higher chip power or a new tray layout changes the flow each tray needs, which changes the vapor leaving each plate, which changes the return lines and the CDU. A cooling system assembled from separately specified parts has to be re-matched by hand every time that happens, while a system built with its fluid, cold plate, and CDU evaluated together can be reworked as one loop.
When a chip maker raises its power target, CurieOS follows the change through every design that depends on it. It reruns the cold plate CFD at the new heat load, recalculates the flow each tray needs and the vapor leaving each plate, resizes the return lines and the CDU's condenser, and checks that the fluid still boils where it should at the loop's pressure. Our engineers then review one updated loop, with every change traced back to the target that triggered it, instead of re-matching three sets of parts.
Our two-phase system is validated at the cold plate, and each stage from here brings more of the loop into the test. Tray-scale testing under our Nimbus program adds flow distribution across a tray's cold plates and validates loop process control with varying heat loads. The full system under Cumulus then runs the fluid, cold plates, and CDU together, with the CDU holding the whole loop at its operating pressure.
Our two-phase system is the first product built on CurieOS, which has carried the program from the fluid to the cold plate and now carries the same requirements and test data into each new stage. It managed the screening that found the fluid and the design of every cold plate since, which is what keeps the system adaptable as each stage adds more of the loop.
If you're specifying cooling for racks planned around 2027 and 2028 GPU platforms, see the full system we're building on our two-phase cooling page.